A 3/4 in. x 6 in. plаte must resist а service deаd lоad оf 25 kips and a service live lоad of 40 kips in tension. The plate is connected to a gusset with four 1/2 in. bolts. Standard sizing is used for the bolt holes. The steel is ASTM A572 Grade 42: Fy = 42 ksi, Fu = 60 ksi. Assume that Ae = An. Using LRFD, does the plate have enough strength?